ePrints@IIScePrints@IISc Home | About | Browse | Latest Additions | Advanced Search | Contact | Help

IEC/IEEE 60255-118-1-2018 Compliance Testing of SRF, SOGI and Park PLLs for Synchrophasors

Kalke, D and Gurrala, G (2022) IEC/IEEE 60255-118-1-2018 Compliance Testing of SRF, SOGI and Park PLLs for Synchrophasors. In: 2022 IEEE International Conference on Electrical, Computer, and Energy Technologies, ICECET 2022, 20 July 2022 - 22 July 2022, Prague.

[img] PDF
2022 IEEE_ICECET 2022_2022.pdf - Published Version
Restricted to Registered users only

Download (884kB) | Request a copy
Official URL: https://doi.org/10.1109/ICECET55527.2022.9872839

Abstract

Synchrophasor measurements received significant attention for power system monitoring and control in the past decade. This paper presents compliance testing of three widely used phase-locked loop (PLL) architectures for synchrophasor estimation as per IEEE standard IEC/IEEE 60255-118-1-2018. Synchronous Reference Frame (SRF) PLL, Second Order Generalised Integrator (SOGI) PLL, and Park PLL are tested as per IEEE standard IEC/IEEE 60255-118-1-2018 for synchrophasor measurement without using any pre and post-processing filters. The tunable parameters for each PLL are varied to determine the range in which they satisfy the performance metrics and comply with the standard. It is found that the PLLs cannot meet all static, dynamic test requirements with a single set of parameters, and the performance of SOGI PLL is superior to SRF and Park PLL.

Item Type: Conference Paper
Publication: International Conference on Electrical, Computer, and Energy Technologies, ICECET 2022
Publisher: Institute of Electrical and Electronics Engineers Inc.
Additional Information: The copyright for this article belongs to Institute of Electrical and Electronics Engineers Inc.
Keywords: Electric power transmission networks; IEEE Standards; Parks; Phasor measurement units; Regulatory compliance, Compliance testing; IEC/IEEE 60255-118-1-2018; IEEE standards; Park phase-locked loop; Power systems monitoring; Second order generalized integrator phase-locked loop; Second-order generalized integrators; Synchronoi reference frame phase-locked loop; Synchronous reference frame; Synchrophasor measurements, Phase locked loops
Department/Centre: Division of Electrical Sciences > Electrical Engineering