Siddagangappa, MC and Mandal, DK (1996) Influence of Electrode Temperature on the Characteristics of a Non Uniform Field System with a Barrier. In: Conference Record of the 1996 IEEE International Symposium on Electrical Insulation, 16-19 June, Montreal,Quebec,Canada, Vol.2, 550 -553.
|
PDF
influence.pdf Download (298kB) |
Abstract
Electrode temperature controlled AC corona discharge inception voltages (CIV) of a nonuniform field electrode system and the characteristics change of CIV in the presence of a barrier is investigated. Reduction in the breakdown voltages of the gap for negative standard impulse applications was observed as the point electrode temperature reached 200°C and the characteristic occurrence was repeated in the presence of a pressboard barrier.
Item Type: | Conference Paper |
---|---|
Publisher: | IEEE |
Additional Information: | Copyright 1990 IEEE. Personal use of this material is permitted. However, permission to reprint/republish this material for advertising or promotional purposes or for creating new collective works for resale or redistribution to servers or lists, or to reuse any copyrighted component of this work in other works must be obtained from the IEEE. |
Department/Centre: | Division of Electrical Sciences > High Voltage Engineering (merged with EE) |
Date Deposited: | 22 Aug 2008 |
Last Modified: | 19 Sep 2010 04:26 |
URI: | http://eprints.iisc.ac.in/id/eprint/6640 |
Actions (login required)
View Item |