Haseeb, M A and Thomas, M Joy (2017) Computation of Very Fast Transient Overvoltages (VFTO) in a 1000 kV Gas Insulated Substation. In: IEEE PES Asia-Pacific Power and Energy Engineering Conference (APPEEC), NOV 08-10, 2017, Bangalore, INDIA.
PDF
Ieee_Appes_2017.pdf - Published Version Restricted to Registered users only Download (1MB) | Request a copy |
Abstract
Very fast transient overvoltages (VFTO) generated in a gas insulated substation (GIS) during disconnector switching operations is one of the major concerns in insulation design of the GIS. Such over voltages can cause malfunctioning of the protection and control circuits in addition to initiating faults inside the gas insulated bus ducts of the substation especially in the presence of metallic particles. In this paper, VFTO have been estimated at various points in a 1000 kV rated substation for all possible valid disconnector switching operations. For the substation studied, the maximum computed overvoltage is 1.58 pu without considering the trapped charge on the busbar. Major frequency components in the simulated VFTO lies in the range of 840 KHz to 30 MHz. Simulations have been carried out using the Electromagnetic Transient Program (EMTP).
Item Type: | Conference Proceedings |
---|---|
Series.: | Asia-Pacific Power and Energy Engineering Conference |
Publisher: | IEEE, 345 E 47TH ST, NEW YORK, NY 10017 USA |
Additional Information: | Copy right for this article belong to IEEE, 345 E 47TH ST, NEW YORK, NY 10017 USA |
Department/Centre: | Division of Electrical Sciences > Electrical Engineering |
Date Deposited: | 18 Apr 2018 18:23 |
Last Modified: | 18 Apr 2018 18:23 |
URI: | http://eprints.iisc.ac.in/id/eprint/59627 |