Srivastava, Sachin and Biswal, Abhinna and Phanindra, KSV and Shenoy, UJ (2015) Behavior of Different Distance Relay Characteristic on Lines Fed From Type-1 and Type-2 WTGU Connected Radially to Grid: A Case Study. In: IEEE Innovative Smart Grid Technologies - Asia (ISGT ASIA 2015), NOV 03-06, 2015, Bangkok, THAILAND.
PDF
ISGT_ASIA_2015.pdf - Published Version Restricted to Registered users only Download (612kB) | Request a copy |
Abstract
Line protection in HV/EHV/UHV lines is primarily by distance protection due to its selective, reliable and secure operation. With the wind farm penetration, the SIRs of lines are going to change drastically throughout the day. A case study has been performed in this paper to study the behavior of dynamic characteristics with respect to these changes. Analytically fault voltages and currents are calculated for the system. Distance relay implemented on hardware has been validated with these waveforms and inferences have been made to give recommendations for characteristics to be applied in practical systems for secure and reliable operation of distance relay.