A Novel Technique for the Computation of Radiated EMI due to Corona on HV Transmission Lines

Nayak, SK and Thomas, Joy M (2003) A Novel Technique for the Computation of Radiated EMI due to Corona on HV Transmission Lines. In: 2003 IEEE International Symposium on Electromagnetic Compatibility, 18-22 August, Boston, Vol.2, 738-742.

[img]
Preview
PDF
novel_technique.pdf

Download (295kB)

Abstract

This paper presents a novel technique for the computation of radiated electromagnetic interference levels due to corona on HV transmission lines. The EMI levels due to corona computed for different lines from around the world matches well with the experimentally measured values, thus validating the present technique. Using the technique developed, it has been shown that the radiated field a an observation point close to the transmission line increases with the line length and reaches almost a constant value for line lengths above 1500 m. The influence of increased spacing between phase conductors is to reduce the radiated field where as the type of phase configuration does not have any influence on the radiated field.

Item Type: Conference Paper
Publisher: IEEE
Additional Information: Copyright 1990 IEEE. Personal use of this material is permitted. However, permission to reprint/republish this material for advertising or promotional purposes or for creating new collective works for resale or redistribution to servers or lists, or to reuse any copyrighted component of this work in other works must be obtained from the IEEE.
Keywords: Electromagnetic interference;Corona;HV Transmission lines