ePrints@IIScePrints@IISc Home | About | Browse | Latest Additions | Advanced Search | Contact | Help

Electromagnetic Field Emission From Gas-to-Air Bushing in a GIS During Switching Operations

Rao, Mohana M and Thomas, Joy M and Singh, BP (2007) Electromagnetic Field Emission From Gas-to-Air Bushing in a GIS During Switching Operations. In: IEEE Transactions on Electromagnetic Comptibility, 49 (2). pp. 313-321.

[img]
Preview
PDF
Electromagnetic.pdf

Download (354kB)

Abstract

Very fast transient overvoltages (VFTOs) and the associated very fast transient currents (VFTCs) generated during switching operations in a gas-insulated substation (GIS) radiate electromagnetic (EM) fields, which in turn can leak into the external environment through apertures like $SF_6$ gas-to-air bushing. Therefore, it becomes necessary to characterize and quantify the EM fields when sensitive control devices are used for the operation of such substations. Keeping this in view, a numerical model using a finite-difference time-domain (FDTD) technique was developed to compute the transient field emission from a 245-kV-rated gasto- air bushing. Shielding effectiveness (SE) of the bushing for these transient fields was evaluated using a derivative Gaussian current excitation of the high-tension (HT) conductor. The variation in EM field levels along the axis of bushing at various radial distances for different frequencies of the transient current were analyzed. The enhancement of the field levels due to the presence of a metallic structure on the ground plane, which simulates the control cubicle or the grounded enclosures of the GIS, were studied. Finally, the emission levels from different bushing models were calculated for the VFTC generated during a switching event, and the dominant frequencies were identified.

Item Type: Journal Article
Publication: IEEE Transactions on Electromagnetic Comptibility
Publisher: IEEE
Additional Information: Copyright 2006 IEEE. Personal use of this material is permitted. However, permission to reprint/republish this material for advertising or promotional purposes or for creating new collective works for resale or redistribution to servers or lists, or to reuse any copyrighted component of this work in other works must be obtained from the IEEE.
Keywords: Electromagnetic interference (EMI);Finite difference time-domain (FDTD);Gas-insulated substation (GIS);Switching;Very fast transient currents (VFTCs);Very fast transient overvoltages (VFTOs)
Department/Centre: Division of Electrical Sciences > High Voltage Engineering (merged with EE)
Date Deposited: 11 Sep 2007
Last Modified: 19 Sep 2010 04:39
URI: http://eprints.iisc.ac.in/id/eprint/11818

Actions (login required)

View Item View Item