Effect of charge accumulation on the electric field distribution along spacer surfaces

Chakravorti, S and Siddagangappa, MC (1995) Effect of charge accumulation on the electric field distribution along spacer surfaces. In: International Symposium on High Voltage Engineering, 28 August-1 September 1995, Graz, Austria, Vol, 8 8352/1-4.

Full text not available from this repository. (Request a copy)

Abstract

The effects of surface charge accumulation on electric field distribution around solid spacers bridging the uniform field gap stressed with DC voltage relevant to DC gas-insulated substations (GIS) have been studied numerically by the charge simulation method. The numerical evaluations of charge accumulation are found to agree with experimental data reported by other researchers. The present work reports on an analysis of resultant stress distribution on a few spacer configurations for which accumulated surface charges modify the electric field and, for a certain case study, charge accumulation has resulted in reduced resultant peak stress.

Item Type: Conference Paper
Publisher: Institute of High Voltage Engineering
Additional Information: Copyright of this article belongs to Institute of High Voltage Engineering.
Department/Centre: Division of Electrical Sciences > High Voltage Engineering (merged with EE)
Date Deposited: 19 Sep 2007
Last Modified: 11 Jan 2012 08:32
URI: http://eprints.iisc.ac.in/id/eprint/10960